Plug in the variables and find the answers to common treatment formulas.
Formulas
MGD x 8.34 x ppm Influent = Total pounds entering plant
MGD x 8.34 x ppm Effluent = Total pounds leaving plant
Pounds entering plant - Pounds leaving plant = Pounds removed
Pounds entering plant - Pounds leaving plant / Pounds entering plant x 100 = % Removal efficiency
Top^
Feed Rate / (GPM x .012) = Calculated Residual
Calculated Residual - Measured Residual = Chlorine Demand
Pumping Level-Static Level=Drawdown in feet
GPM/Drawdown=Specific Capacity in gpm per foot